|Table of Contents|

Influence of Load Distribution on Long-term Operation Characteristics of Ground Source Heat Pump System

《南京理工大学学报》(自然科学版)[ISSN:1005-9830/CN:32-1397/N]

Issue:
2011年02期
Page:
155-159
Research Field:
Publishing date:

Info

Title:
Influence of Load Distribution on Long-term Operation Characteristics of Ground Source Heat Pump System
Author(s):
YU Yan-shunMA Juan
School of Energy and Power Engineering,NUST,Nanjing 210094,China
Keywords:
ground source heat pump system load distribution thermal incubation effect long-term operation characteristics
PACS:
TU831.3
DOI:
-
Abstract:
In order to study the long-term operation characteristics of the ground source heat pump system(GSHPs)in various building load distributions,the heat transfer model considering the groundwater seepage of the underground heat exchanger system is established.The 10-year continuous simulations of GSHPs for hotel buildings in Beijing,Harbin and Shanghai with the typical load distribution are performed,and the long-term operation characteristics of GSHPs in regions are analyzed.The results show that the influence of thermal incubation effect on operation characteristics can be ignored in Beijing which is a load balance region.However,in Harbin(with load ratio 6.6∶1)region,the maximum and minimum outlet temperatures of the pipe decrease 3.8 ℃,and in Shanghai(with load ratio 1∶3.6)they increase 5.6 ℃ in the 10-year operation,and the amplitude of tempera-tures are 0.38 ℃/a and 0.56 ℃/a,respectively.

References:

[1] 《机电信息》调研部. 2005 年国内地源热泵市场调 研[J]. 机电信息, 2006, 19: 10 - 14.
[2] Yang Wei,Zhou Jin,Xu Wei,et al. Current status of ground-source heat pumps in China[J]. Energy Policy, 2010, 38: 323 - 332.
[3] 吕悦,杨立平,周沫,等. 国内地源热泵应用情况调 查报告[J]. 工程建设与设计,2005( 6) : 5 - 10.
[4] 马最良,吕悦. 地源热泵系统设计与应用[M]. 北 京: 中国建筑工业出版社,2007.
[5] 吕悦. 应大力推动地源热泵城市级区域推广应用 [J]. 工程建设与设计,2006,8 : 34 - 36.
[6] 刊通讯员. 沈阳成为全国地源热泵推行城市[J]. 煤 气与热力, 2007, 27( 4) : 24.
[7] 董菲,倪龙,姚杨,等. 浅层岩土蓄能加浅层地温能 才是地源热泵可持续利用的低温热源[J]. 暖通空 调, 2009, 39( 2) : 70 - 72.
[8] 殷平. 地源热泵在中国[J]. 现代空调,2001,3: 1 - 8.
[9] Gu Yian,O’Neal D L. Development of an equiva-lent diameter expression for vertical U-tube used in groundcoupled heat pumps [J]. ASHARE Transac-tions, 1998, 104( 2) : 347 - 355.
[10] Gu Yian,O’Neal D L. Modeling the effect of backfills on U-tube ground coil performance [J]. ASHRAE Transactions, 1998, 104( 2) : 356 - 365.
[11] 马娟. 土壤耦合热泵系统的长周期运行特性研究 [D]. 南京: 南京理工大学动力工程学院,2009.

Memo

Memo:
-
Last Update: 2012-04-30